| Sign In | Join Free | My xpandrally.com | 
              
  | 
      
Brand Name : KINGSINE
Model Number : K3163i
Certification : CE/ISO9001
Place of Origin : China
MOQ : 100 sets/month
Price : Negotiation
Payment Terms : L/C,L/C
Supply Ability : 100 sets/month
Delivery Time : 15 working days
KINGSINE K3163i Differential Relay Testing Protection Relay Test Support IEC61850
All-in-One design, weight < 17.5kg;
High Power & Accuracy with 6x35A & 4x310V analog outputs;
Complying IEC61850 Sampling Value & GOOSE;
The ever-expanding test library templates;
Optional advance functions like energy meter and transducer calibration etc.
| ● | Universal Relay Test Applications | 
| ● | 10 Channels (6x35A & 4x310V) outputs, Each output channels are independent and simultaneous control of magnitude, Phase angle and frequency values, able to inject DC, AC sine wave and up to 60x harmonics. | 
| ● | 13 Low-level channels outputs up to 8Vac/10Vdc max. | 
| ● | 100/1000Mbit Fiber port for SMV and GOOSE simulations | 
| ● | Variable battery simulator, DC 0-350V, 140Watts max. | 
| ● | Transient play back up to 3KHz | 
| ● | Fully function KRT software testing modules | 
| ● | Graphical test modules and templates for testing of various relays | 
| ● | Quick relay testing facility in Manual mode | 
| ● | Shot/Search/Check, Point & Click testing | 
| ● | RIO/XRIO import & export facility | 
| ● | Switch on to fault test(SOTF) | 
| ● | Power system model for dynamic testing | 
| ● | Online Vector display | 
| ● | Automatic test results assume | 
| ● | Automatic test report creation | 
| ● | Inbuilt GPS and IRIG-B sync end-to-end testing | 
| ● | Anti-clipping detect, Wrong wiring connect alarm and self-protect, overload and overheat protection | 
| ● | 3-Years guarantee of free repair and life-long maintenance | 
| ● | Lightweight, <18Kg | 
| ● | Free software upgrade | 
| ● | Complied IEC61850-9-1, IEC61850-9-2, IEC60044-7/8, etc | 
| ● | Transducer calibration (0.02 class) | 
| ● | Energy meter calibration (Mechanical & Electronic meters) | 
| Items | ANSI® No. | 
| IEC61850 numerical IEDs relay & merge unit | |
| Distance protection relay | 21 | 
| Synchronising or synchronism-check relays | 25 | 
| Undervoltage relays | 27 | 
| Directional Power relays | 32 | 
| Undercurrent or underpower relays | 37 | 
| Negative sequence overcurrent relays | 46 | 
| Overcurrent/ground fault relays | 50 | 
| Inverse time overcurrent/ground fault relays | 51 | 
| Power factor relays | 55 | 
| Overvoltage relays | 59 | 
| Voltage or current balance relays | 60 | 
| Directional overcurrent relays | 67 | 
| Directional ground fault relays | 67N | 
| DC overcurrent relays | 76 | 
| Phase-angle measuring or out-of-step protection relays | 78 | 
| Automatic reclosing devices | 79 | 
| Frequency relays | 81 | 
| Motor overload protection relays | 86 | 
| Differential protection relays | 87 | 
| Directional voltage relays | 91 | 
| Voltage and power directional relays | 92 | 
| Tripping relays | 94 | 
| Voltage regulating relays | |
| Overimpedance relays, Z> | |
| Underimpedance relays, Z | |
| Time-delay relays | 
| Voltage Outputs | ||
| Output Range & Power | 4×310 V ac (L-N) | 124 VA max each | 
| 3×350 V dc (L-N) | 140 W max each | |
| Accuracy | ±2mV @ <2V ac <0.015%Rd+0.005Rg Typ. @ 2~310V ac <0.04%Rd+0.01Rg Guar. @ 2~310V ac  | 
		|
| ±10mV @ <5V dc ±0.5% @ ≥5V dc  | 
		||
| Voltage Range | Range I : 30V | |
| Range II : 310V | ||
| Automatic Range | ||
| DC Offset | <20mV Typ./ <100mV Guar | |
| Resolution | 1mV | |
| Distortion | <0.015%Typ. / <0.05% Guar. | |
| Current Outputs | ||
| Output Range & Power | 6×35A ac (L-N) | 480 VA max each | 
| 3×70A ac (2L-N) | 850 VA max each | |
| 1×100A ac (6L-N) | 1200 VA max | |
| 3×20A dc (L-N) | 300W max each | |
| Accuracy | ±1mA @ <0.5A ac <0.02%Rd+0.01Rg Typ. @ 0.5A~35A ac <0.05%Rd+0.02Rg Guar. @ 0.5A~35A ac  | 
		|
| ±5mA @ <1A dc ±0.5% @ ≥1A dc  | 
		||
| Current Range | Range I: 3A | |
| Range II: 35A | ||
| Automatic Range | ||
| DC Offset | <3mA Typ./ <10mA Guar | |
| Resolution | 1mA | |
| Distortion | <0.025%Typ. / <0.07% Guar. | |
| Low-Level Output | ||
| Quantity | 13 Channels, 16 pin combination female socket | |
| Voltage Outputs Range | AC 0~8V, DC 0~10V | |
| Current Outputs Range | Nominal 2mA, 10mA max transient | |
| Output Power | ≥0.5VA | |
| Accuracy | (0.01~0.8 Vrms):<0.05% Typ. / <0.1% Guar. (0.8~8 Vrms): <0.02% Typ. / <0.05% Guar.  | 
		|
| Resolution | 0.25mV | |
| Distortion (THD%) | <0.05% Typ. / <0.1% Guar. | |
| Frequency Range | 0~3000KHz | |
| DC Offset | <0.15mV Typ. / <1.5mV Guar. | |
| Frequency & Phase Angle | ||
| Frequency Range | DC~1KHz, 3KHz transient | |
| Frequency Accuracy | ±0.5ppm | |
| Frequency Resolution | 0.001 Hz | |
| Phase Range | -360°~360° | |
| Phase Accuracy | <0.02° Typ. / <0.1° Guar. 50/60Hz | |
| Phase Resolution | 0.001° | |
| Aux. DC Voltage Source (Battery simulator) | ||
| Range | 0~350V @ 140W max | |
| Accuracy | 0.5%Rg Guar. | |
| Binary Input | ||
| Quantity | 8pairs | |
| Type | wet/dry, measurement | |
| Threshold | 10~600Vdc or potential free, Programmable | |
| Time resolution | 10us | |
| Sampling Rate | 10KHz | |
| Debounce time | 0~25ms (Software Controlled) | |
| Time range | Infinite | |
| Time errors | ±1ms @ ≤1s, ±0.1% @ >1s | |
| Galvanic isolation | 4 isolated with each 2 pairs | |
| Binary Output (Relay Type) | ||
| Quantity | 4pairs | |
| Type | Potential free relay contacts, software controlled | |
| Break Capacity AC | Vmax: 400Vac / Imax:8A / Pmax:2500VA | |
| Break Capacity DC | Vmax: 300Vdc / Imax:5A / Pmax:150W | |
| Binary Output (Semiconductor Type) | ||
| Quantity | 4pairs | |
| Type: | Open-collector, Combination type female | |
| Break Capacity DC | 5~15Vdc / 5mA, 10mA max AC not permit  | 
		|
| Response time: | 100us | |
| Synchronization | ||
| Synchronization Mode | GPS, SMA type antenna connector IRIG-B (Optical fiber, FT3 type)  | 
		|
| Power supply & Environment | ||
| Nominal Input Voltage | 100~240Vac | |
| Permissible Input Voltage | 85~260Vac, 125~350VDC | |
| Nominal Frequency | 50/60Hz | |
| Permissible Frequency | 45Hz~65Hz | |
| Power Consumption | 1500 VA max | |
| Connection Type | Standard AC socket 60320 | |
| Operating Temperature | -10℃~55℃ | |
| Storage Temperature | -20℃~70℃ | |
| Humidity | <95%RH, non-condensing | |
| Others | ||
| PC Connection | RJ45 Ethernet, 10/100M | |
| Grounding Terminal | 4mm banana socket | |
| Weight | 17.5 Kg | |
| Dimensions(W x D x H) | 
			 468×375×164(mm)  | 
		|
(Optional Modules)
IEC61850 functions: 
| ● | Fully complying IEC61850 Sampling value and GOOSE; (IEC61850-9-1, IEC61850-9-2/(LE), IEC60044-7/8) | 
| ● | Able to simultaneously output sampling value and analog signals, or subscriber and publish GOOSE message and relay contact binary I/O function. | 
| ● | Up to 36 sampling value channels can be mapped. | 
| IEC61850 Fiber & GOOSE Ethernet Ports (Optional Function) | |
| Fiber Ports | 2 x 100Base-FX Full Duplex, LC type (Optional to 10/100Mbit, Ethernet RJ45 type)  | 
		
| Fiber Type | 62.5/125um (Multiple optical fiber, Orange Red) | 
| Wavelength | 1310nm | 
| Transmit Distance | >1Km | 
| Indicator | Spd Green(light): Valid connection Link/Act Yellow(Blinking): Data exchanging  | 
		
| Note: | Hardware is ready, to be active | 
| DC Measurement Input Hardware is ready, to be active | ||
| Voltage Input | Range | 0~±10V dc | 
| Max Input | ±11V dc | |
| Accuracy | <0.05% rg Typ. <0.1% rg Guar. | |
| Input Impedance | 1M ohm | |
| Current Input | Range | 0~±1mA / 1~±20mA, auto range | 
| Max Input | 600mA | |
| Accuracy | <0.05% rg Typ. <0.1% rg Guar. | |
| Input Impedance | 15 ohm | |
| Energy Meter Calibration Hardware is ready, to be active | |
| Sensor Usage | Mechanical meters / Electronic meters | 
| Sensor Output | High lever:>4.5V, Low level:<0.2V | 
| Pulse Input | 1 pulse input port, 5Vdc high level valid only. | 
| Pulse Range | 500KHz pulse input Max. | 
| Pulse Output | 1 Transistor output, Open-collector, 5Vdc/5mA | 
| Model | Current Outputs | Voltage Outputs | Optional | 
| K3166i | 6×35A @ 450VA max 3×70A @ 850VA max  | 
			7×310V @ 90VA max | ● IEC61850 SV ● IEC61850 GOOSE ● Energy meter cal. ● Transducer cal.  | 
		
| K3163i | 6×35A @ 450VA max 3×70A @ 850VA max  | 
			4×310V @ 124VA max | |
| K3130i | 3×35A @ 450VA max | 4×310V @ 124VA max | 
| 
                                             | 
                
                        KINGSINE K3163i Differential Relay Testing Protection Relay Test Support IEC61850 Images |